额定电压0.6/1kV聚氯乙烯绝缘电力电缆
PVC insulated power cables with rated voltages 0.6/1kV
本产品适用于配电网、工业装置等领域,用于固定敷设在交流50Hz、额定电压0.6/1kV的电力输配电线路上,主要功能是输送电能。本产品为通常条件下使用的产品,不适用一些特殊条件的场合,如架空、水下、船用、海底、核电站等。
阻燃聚氯乙烯绝缘电缆适用于具有阻燃要求的场合。
耐火聚氯乙烯绝缘电缆适用于地下铁道、地下商场、大型购物中心、高层建筑等人口稠密、通风受限的场合。
This product is applicable to being fixedly laid on the transmission and distribution line of alternative current rating 50Hz and rated voltage up to 0.6/1.0Kv with the use for power transmission, which is applied to the range of distribution network, industrial equipments, etc.
This product is the nomal used cable, not suitable for some special places, such asunderwater, ship, nuclear station, etc.
本产品电缆除具有可靠的电气性能外,还具有较强的防止化学腐蚀性,耐酸、碱和有机溶剂,电缆不受敷设落差的限制,可在任何落差甚至垂直的场合敷设。
The product has good performance on electrical characteristic, chemical resistance, such as acid resistance, alkali resistance and organic solvent resistance. The product can be laid on any head drop condition even vertically in any place, that is to say, the cable can be laid without limit on head drop.
GB/T 12706.1-2002 额定电压1 kV(Um=1.2 kV)到35 kV(Um=40.5 kV)挤包绝缘电力电缆及附件
第1部分:额定电压 1kV(Um=1.2 kV)和3 kV(Um=3.6 kV)电缆
Power cables with extruded insulation and their for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3 kV(Um=3.6 kV)
IEC 60502-1:1997 额定电压1 kV(Um=1.2 kV)到30 kV(Um=36 kV)挤包绝缘电力电缆及附件
第2部分:额定电压 1 kV(Um=1.2kV)和3 kV(Um=3.6kV)电缆
Power cables with extruded insulation and their for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3 kV(Um=3.6 kV)
Q/12BJ4973-2002 额定电压0.6/1kV 五芯塑料绝缘电力电缆
Q/12BJ4973-2002 Five cores extruded plastic insulated power cables with rated voltages 0.6/1kV
GB/T 3956-1997 电缆的导体
GB/T 3956-1997 Conductor of Cables
GB/T19666-2005 阻燃耐火电线电缆通则
GB/T 19666-2005 General Rules of flame-retarding and fireproof cables
1、 额定电压Rated Voltage
电缆额定电压U0/U(Um)为:0.6/1(1.2)kV
Rated Voltage of cable U0/U(Um):0.6/1(1.2)kV
其中:Notes:
U0:电缆设计用的导体对地或金属屏蔽之间的额定工频电压;
Rated A.C. Voltage between conductor and ground/metal screen;
U:电缆设计用的导体间的额定工频电压;
Rated A.C. Voltage between conductors
Um:设备可承受的“最高系统电压“的最大值。
The maximum system voltage which the equipments can be beared
电缆的额定电压应适合电缆所在系统的运行条件。为了便于选择电缆,将系统划分为下列三类:
The rated voltage of cable shall be applicable to system operation condition where the cable lain in. According to cable selecting, the system will be described as 3 types as follow:
——A类:任一相导体与地或接地导体接触时,能在1min内与系统隔离。
System category A —When any phase of cable conductor is contacting with earth conductor, the cable will be isolated with the system.
——B类:可在单相接地故障时作短时运行,但任何情况下不宜超过8h,每年接地故障总持续时间不宜超过125h。
System category B ─The system is allowed to run for 8 hours, when the single-phase earth fault is existing. And the total earth-fault time of 1 year won't be above 125 hours.
——C类:包括不属于A类和B类的系统。
System category C ─They are including all systems besides A and B.
注:在系统接地故障不能立即自动解除时,故障期间加在电缆绝缘上过高的电场强度,会在一定程度上缩短电缆寿命。如系统预期会经常地运行在持久的接地故障状态下,该系统应划为C类。
When the system earth fault can't be removed automatically, the life of cable will be shortened in some degree because of the over-high electric stess beared by cable insulation.
用于三项系统的电缆,U0的推荐值见表1。
The recommended figure of U0 see the table 1, which are suitalbe for the three systems.
表1 额定电压U0推荐值
Table1 The recommended figure of U0
系统最高电压Um/kV The maximum system voltageUm/kV | 额定电压/kV Rated Voltage/ kV | |
A类、B类 System categories A and B | C类 Systems categories C | |
1.2 | 0.6 | 1.2 |
2、 导体额定工作温度
The rated temperature of conductor
电缆导体的最高额定工作温度为70℃。
The maximum assigned temperature of the cable conductor is 70℃。
短路时(最长持续时间不超过5s)电缆导体的最高温度不超过160℃。
During having a short circuit, lasting less than 5 seconds, the maximum temperature of the cable conductor shall not be above 160℃.
3、 敷设环境温度
Ambient temperature for laying
电缆敷设时的环境温度应不低于0℃,否则需要事先预热。
The ambient temperature for laying shall be above 0℃, if not the cable need be preheated.
4、 安装弯曲半径
The bend radius
安装时电缆最小弯曲半径见表2。
The minimun bend radius of the cable see the table 2
表2 电缆安装时最小弯曲半径
Table2 The minimun bend radius of the cable
项目 Item | 单芯电缆 Single -core | 三芯电缆 Three -core | ||
无铠装 Unarmored | 有铠装 Armored | 无铠装 Unarmored | 有铠装 Armored | |
安装时的电缆最小弯曲半径 Minimun bend radius of the cable in course of installation | 20D | 15D | 15D | 12D |
靠近连接盒和终端的电缆的最小弯曲半径 The minimun bend radius of the cable close to the junction box and terminal | 15D | 12D | 12D | 10D |
注:D为电缆外径(mm)。Note:D is outer diameter of the cable |
5、 敷设方式
电缆没有敷设落差限制。
There is no limit of head drop during the cable laying.
电缆允许敷设在室内、室外、空气中和土壤中,允许局部有积水。
The cable may be laid in indoor, outdoor, air and soil. The cable may be immersed in water locally.
电缆敷设方式可以是隧道、管道、电缆沟、桥架、排管,铠装电缆允许直埋地下,钢丝铠装电缆允许垂直敷设。
The cable may be laid in tunnel, pipe, trench, conduit and on cable bridge. The amoured cable can be laid undergroud, and the wire- amoured cable can be laid vertically.
单芯电缆不允许敷设在磁性金属管内。
The single core cable mustn't be laid in the magnetic metal pipes.
电缆敷设环境应有良好的散热条件。
The enviroment of cable laying shall be in good heat dissipation condition.
6、 电缆敷设时导体最大允许牵引力和电缆最大允许侧压力
The maxium allowed haul-off force and lateral pressure of cable
导体最大允许牵引力计算方法:he calculating method of the maxium allowed haul-off force
——铜导体:F=70×S(N/mm2)。
——铝导体:F=40×S(N/mm2)。
侧压力计算方法:P=F÷R(N/m),最大允许侧压力不超过3000N/m。
S-导体截面,mm2;conductor section
P-侧压力,N/m;lateral pressure
R-电缆弯曲半径,m;Bend radius
7、 电缆运输和保管要求
The requirements on transportation and storage:
电缆盘不允许平放。
The cable reels shall not be delivered and stored in flat state
运输中严禁从高处扔下装有电缆的电缆盘,严禁机械损伤电缆。
It is strictly forbidden to push the cable reel from the high level in order to prevent the cable from damages
电缆如果需要分段使用,电缆分段后必须用防水封帽将电缆头密封,防止进水。
If the cable should be used sectionally, the head of the cable must be sealed in order to prevent water intake.
1、代号Code
导体代号Conductor code
铜导体(省略)Copper conductor ( omitted )………………………………………………………………T
铝导体aluminium conductor…………………………………………………………………………………L
绝缘代号Insulation code
聚氯乙烯绝缘 cross-linking polyethylene(XLPE) insulated……………………………………………V
护套代号1)Sheath code
聚氯乙烯护套 polyvinyl chloride and sheath………………………………………………………………V
聚乙烯护套 polyethylene sheath……………………………………………………………………………Y
铠装代号Amour code
双钢带铠装steel tape armoured ……………………………………………………………………………2
细圆钢丝铠装thin steel-wire armoured ……………………………………………………………………3
粗圆钢丝铠装thick steel-wire armoured ……………………………………………………………………4
双非磁性金属带2)铠装 Double non-magnetic metal tape amoured………………………………………6
非磁性金属丝3)铠装Non-magnetic metal-wire amoured……………………………………………………7
外护套代号Outer sheath code
聚氯乙烯外护套 polyvinyl chloride outer sheath …………………………………………………………2
聚乙烯外护套 polyethylene outer sheath …………………………………………………………………3
系列代号Series code
阻燃系列fire-safe series
阻燃A类flame-retardant class A …………………………………………………………………………ZA
阻燃B类flame-retardant class B …………………………………………………………………………ZB
阻燃C类flame-retardant class C …………………………………………………………………………ZC
阻燃D类flame-retardant class D …………………………………………………………………………ZD
耐火系列fire-safe series
阻燃A类耐火flame-retardant class A fire-safe…………………………………………………………ZAN
阻燃B类耐火flame-retardant class B fire-safe…………………………………………………………ZBN
阻燃C类耐火flame-retardant class C fire-safe…………………………………………………………ZCN
阻燃D类耐火flame-retardant class D fire-safe…………………………………………………………ZDN
注:Note
1) 包括挤包的内衬层和隔离套等。
Including the extruding inner covering and separating tape.
2) 非磁性金属带包括不锈钢带、铝带等,若订货时未注明,采用何种材料由制造方确定。
Non-magnetic metal tapes are including stainless steel tape, aluminium tape, etc. The materials will determined by the manufacturer, if the buyer not mentioned.
3) 非磁性金属丝包括不锈钢丝、铜丝、铝丝等,若订货时未注明,采用何种材料由制造方确定。
Non-magnetic metal wires are including stainless steel tape, aluminium tape, etc. The materials will determined by the manufacturer, if the buyer not mentioned.
2、产品表示方法Expressed method of product
产品用型号(型号中有数字代号的电缆外护层,数字前的文字代号表示内护套)、规格(额定电压、芯数、标称截面)和标准编号表示。
The product is described as type (figure code of cable outer sheath, the word code in front of the figure means inner sheath), specification(rated voltage, cores numbers, sectioal area ) and standards code.
3、产品型号组成The consistant of specifications
产品型号的组成和排列顺序如下:
The consistant of specification, as follow:
①普通电缆型号组成
②阻燃耐火电缆型号组成
注:电力电缆型号组成中绝缘通常作为系列代号。
Note:The insulation in the cable specifications are the series code.
4、产品表示方法 Expressed method of product
示例:铝芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆,额定电压0.6/1kV,3+2芯,标称截面150mm2,表示为:
VLV22-0.6/1 3*150+2*70 GB/T 12706.1-2002 Q/12BJ4973-2002
Example: Aluniminum conductor PVC insulated, steel tape armoured and PVC sheathed power cables, rated Voltages 0.6/1kV, 3+2 cores, Nominal cross area 150mm2, see the following:
VLV22-0.6/1 3*150+2*70 GB/T 12706.1-2002 Q/12BJ4973-2002
示例:铜芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆,额定电压为0.6/1 kV ,2芯,标称截面185mm2, 表示为:
VV22-0.6/1 2*185 GB/T12706.1-2002
Example: Copper conductor PVC insulated, steel tape armoured and PVC sheathed power cables, rated Voltages 0.6/1kV, 2 cores, Nominal cross area 185mm2, see the following:
VV22-0.6/1 2*185 GB/T12706.1-2002
铜芯聚氯乙烯绝缘(聚氯乙烯内护套)钢带铠装聚氯乙烯护套阻燃C类电力电缆,额定电压0.6/1kV,3芯,标称截面150mm2,表示为:
ZC-VV22-0.6/1 3*150 GB/T19666-2005/GB/T12706.1-2002
Example: Copper conductor PVC insulated, steel tape armoured and PVC sheathed flame-retardant class C power cables, rated Voltages 0.6/1kV, 3croes, Nominal cross area 150mm2, see the following:
ZC-VV22-0.6/1 3*150 GB/T19666-2005/GB/T12706.1-2002
铜芯聚氯乙烯绝缘(聚氯乙烯内护套)钢带铠装聚氯乙烯护套耐火电力电缆,额定电压0.6/1kV,3+2芯,标称截面150mm2,表示为:
NHVV22-0.6/1 3*95+2*50 GB/T19666-2005/ Q/12BJ4973-2002
Example: Copper conductor PVCinsulated, steel tape armoured and PVC sheathed flame-retardant class C fire-safe power cables, rated Voltages 0.6/1kV, 3+2cores, Nominal cross area 150mm2, see the following:
NHVV22-0.6/1 3*95+2*50 GB/T19666-2005/ Q/12BJ4973-2002
1、产品型号Type of product
产品常用型号见表3。
For the common product types , please see the table 3
表3 产品型号
Table 3 Type of product
型号 Type | 产 品 名 称 Name of product | 适用范围及环境 Applicability and urroundings | |
铜 芯 Copper core | 铝 芯 Aluminium core | ||
VV | VLV | 聚氯乙烯绝缘聚氯乙烯护套电力电缆 PVC insulated PVC sheath power cable | 室内、隧道及电缆沟等场所,不能承受机械外力。单芯电缆不允许敷设在磁性管道中。 For laying indoors 、 intunnel or cable trench,unable to bear external mechan-icalforces.Single-core cable in magnetic duct is not permissible |
VY | VLY | 聚氯乙烯绝缘聚乙烯护套电力电缆 PVC insulated PE sheath power cable | |
VV22 | VLV22 | 聚氯乙烯绝缘双钢带铠装聚氯乙烯护套电力电缆 PVC insulated steel tape armoured PVC sheath power cable | 室内、隧道、电缆沟内,或埋地敷设等,能承受一定机械外力,但不能承受大的拉力。 For laying indoors 、 in tunnel, cable trench, or direct in ground,able to bear external mechanicalforces, but unable to bear large pulling force 。 |
VV23 | VLV23 | 聚氯乙烯绝缘双钢带铠装聚乙烯护套电力电缆 PVC insulated steel tape armoured PE sheath power cable | |
VV32 | VLV32 | 交联聚乙烯绝缘细圆钢丝铠装聚氯乙烯护套电力电缆 PVC insulated thin steel-wire armoured PVC sheath power cable | 室内、隧道、电缆沟、竖井或埋地敷设等,能承受机械外力和一定的拉力。 For laying indoors 、 in tunnel, cable french, well or direct in ground,able to bear external mechanical forces, and certain force 。 |
VV33 | VLV32 | 聚氯乙烯绝缘细圆钢丝铠装聚乙烯护套电力电缆 PVC insulated thin steel-wire armoured PEsheath power cable | |
VV42 | VLV42 | 聚氯乙烯绝缘粗钢丝铠装聚氯乙烯护套电力电缆 PVC insulated thin steel –wire armoured PVC sheath power cables | |
VV43 | VLV43 | 聚氯乙烯绝缘粗钢丝铠装聚乙烯护套电力电缆 PVC insulated thin steel –wire armoured PE sheath power cables |
2、产品规格 Specification of product
产品额定电压、导体标称截面和芯数见表4。
For product rated voltage, conductor sectiona and the numbers of cores, please see the table 4.
表4 产品规格
Table 4 Specification of prouduct
型 号 Type | 芯数 Number of cores | 标称截面 Nominal cross area(㎜2) | |
VV,VY - VV22,VV23 | - VLV,VLY VLV22,VLV23 | 1 | 1.5-300 2.5-300 10-300 |
VV,VY - VV22 VV23 | - VLV,VLY VLV22 VLV23 | 2 | 1.5-185 2.5-185 4-185 |
VV,VY - VV22 VV23 VV32 VV33 VV42 VV43 | VLV,VLY - VLV22 VLV23 VLV32 VLV33 VLV42 VLV43 | 3 | 1.5-300 2.5-300 4.0-300 16-300 16-300 |
VV,VY VV22 VV23 | VLV,VLY VLV22 VLV23 | 4 | 4-185 4-185 |
VV,VY VV22 VV23 | VLV,VLY VLV22 VLV23 | 3+1 | 4-185 4-185 |
VV,VY VV22 VV23 | VLV,VLY VLV22 VLV23 | 3+2、4+1 | 10-300 10-300 |
以上所有的型号和产品规格中,阻燃电缆型号前加ZRA、ZRB、ZRC、ZRD,耐火电缆电缆型号前加NH,无卤低烟阻燃电缆电缆型号前加WDZC。
1、导体 Conductor
导体应是符合GB/3956 的第一种或第2种裸退火铜导体或镀金属层退火铜导体,或这两种之一的裸铝导体或铝合金导体;或者第5种裸铜导体或镀金属层退火铜导体。
The conductor shall meet the first one of the requirement of GB/3956 or the second one of that, that is bare anneal copper conductor, or bare aluminium conductor or aluminium alloy, or the fifth one of that, that is bare copper conductor or metal coated anneal copper conductor.
2、耐火层fire resistant layer
耐火电缆导体外双层绕包耐火云母带,云母带绕包必须平整、紧密,不允许有折皱、漏包等缺陷。
The cables are to overlap and wrap two layers of mica tape outside the cable conductor so as to form the fire resistant layer.
3、绝缘Insulation
绝缘应紧密挤包在导体上,且应容易剥离而不损伤绝缘体、导体或镀层。
The insulation layer shall be extruded on the conductor, and it shall be easy to be stripped without damages on insulation, conductor and coating layer.
4、隔离套(有铠装电缆)Inner sheath(Armoured cables)
采用聚氯乙烯(PVC)或聚乙烯(PE)挤包在缆芯上。
The separated sheath is the extruding PVC or PE on the cable cores.
5、铠装 Armoured
多芯电缆采用镀锌钢带或镀锌钢丝,用于交流回路的单芯电缆采用非磁性金属带或金属丝(见第五条)。
金属带采用双层间隙绕包,金属丝采用多根同心绞合。
The amour of the multiple cable shall be zinc-plated steel tape or wire, but the amour of the single cable uesed in AC circuit shall be non-magnetic metal-tape or metal-wire. The tappering mode of metal tape should adopt double layer open tappering, and the mode of metal wire shall mutiple concentric stranding.
注:大量事实证明,采用某种特殊结构铠装(如添加铜丝的隔磁结构)的单芯电缆用于交流回路时均出现电缆发热导致载流量大为下降的现象,所以不推荐采用。
Note: A large number of facts show that the single cable with the special structure amour in the AC circuit exists the heating phenomenon, thus causing the reduction of current capacity. The manufacturer don't suggest to adopt this kind cable.
6、外护套Outer sheath
采用ST2型聚氯乙烯护套料或ST7型聚乙烯(PE)护套料挤包在铠装、绝缘或缆芯上。
The materials of outer sheath are extruding ST2 PVCor ST7 PE on amour, insulation or cable cores.
7、成品电缆的标志Cable marks
成品电缆的外护套表面印有厂名、型号、额定电压、芯数、标称截面和米数的连续标志。
The outer sheath of the cable shall have the following information printed at regular intervals throughtout the length of the cable: Manufacturer's Name, Type of cable, Rated Voltage, the numbers of cores, Sectional Area and Meters Number of Continuous Marks.
8、 产品结构示意图Pictures of products structure